The following guide specification is
presented in an easy-to-copy-and-paste format. In addition, if you prefer, you may download this guide specification in .doc or .pdf formats: DFR2 & DFR3 3-Part Guide Spec (.doc) DFR2 & DFR3 3-Part Guide Spec (.pdf) |
|||||||||||||||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||||||||||||||
|
SPECIFICATION Sections 07 90 00 / 07 95 00 EMSHIELD DFR2 / EMSHIELD DFR3 by EMSEAL Preformed, Pre-Compressed, Self-Expanding, Fire Rated Sealant System with Silicone Pre-Coated Surface, Watertight, Traffic Durable, 2 or 3 Hour Rated, Primary Seal for Horizontal Joints
****NOTE to specifier: select DFR2 for two-hour applications and DFR3 for three-hour applications and delete the other or if using both systems make reference to respective locations in the spec and on the drawings**** PART 1 – GENERAL
Standard Submittal Package – Submit
typical expansion joint drawing(s) indicating pertinent
dimensions, general construction, expansion joint
opening dimensions and product information.
Sample of material is required at time
of submittal.
All products must be identified by a UL
listing number and must be listed in the UL and ULC
Online Certification Directories as proof that they have
been tested according to UL 2079 and manufactured under
UL’s "Follow Up" service.
All products must be certified by
independent laboratory test report to be free in
composition of any waxes or wax compounds using FTIR and
DSC testing.
All products shall be certified in
writing to be: a) capable of withstanding 150°F (65°C)
for 3 hours while compressed down to the minimum of
movement capability dimension of the basis of design
product (-25% of nominal material size) without evidence
of any bleeding of impregnation medium from the
material; and b) that the same material after the heat
stability test and after first being cooled to room
temperature will subsequently self-expand to the maximum
of movement capability dimension of the basis-of-design
product (+25% of nominal material size) within 24 hours
at room temperature 68°F (20°C). Product Delivery, Storage and Handling Deliver products to site in
Manufacturer’s original, intact, labeled containers.
Handle and protect as necessary to prevent damage or
deterioration during shipment, handling and storage.
Store in accordance with manufacturer’s installation
instructions. Basis-of-Design All joints shall be designed to meet the
specified performance criteria of the project as
manufactured by: (USA & International) EMSEAL JOINT
SYSTEMS, LTD 25 Bridle Lane, Westborough, MA 01581-2603,
Toll Free: 800-526-8365. (Canada) EMSEAL, LLC 120
Carrier Drive, Toronto, Ontario, Canada M9W 5R1 Toll
Free: 800-526-8365. www.emseal.com
Alternate manufacturers must demonstrate
that their products meet or exceed the design criteria
and must submit certified performance test reports
performed by nationally recognized independent
laboratories as called for in section 1.02 Submittals.
Submittal of alternates must be made three weeks prior
to bid opening to allow proper evaluation time. Quality Assurance The General Contractor will conduct a
pre-construction meeting with all parties and trades
involved in the treatment of work at and around
expansion joints including, but not limited to,
concrete, mechanical, electrical, HVAC, landscaping,
masonry, curtain wall, waterproofing, fire-stopping,
caulking, flooring and other finish trade
subcontractors. All superintendents and foremen with
responsibility for oversight and setting of the joint
gap must attend this meeting. The General Contractor is
responsible to coordinate and schedule all trades and
ensure that all subcontractors understand their
responsibilities in relation to expansion joints and
that their work cannot impede anticipated structural
movement at the expansion joints, or compromise the
achievement of watertightness or life safety at
expansion joints in any way.
Warranty – Manufacturer’s standard
warranty shall apply.
LEED Building Performance Requirements: The VOC of the silicone must not exceed 50 grams/liter. PART 2 – PRODUCT
Provide EMSHIELD DFR2 / EMSHIELD DFR3 as
manufactured by EMSEAL JOINT SYSTEMS LTD and as
indicated on drawings for horizontal-plane expansion
joint locations.
Sealant system shall be comprised of the
following components: 1) fire-retardant-impregnated foam
pre-coated on the underside with an intumescent
fire-proofing material, 2.) pre-coated on the traffic
surface with highway-grade, fuel resistant silicone, 3)
field-applied epoxy adhesive primer, 4) field-injected
silicone sealant bands. Impregnation agent to have
proven non-migratory characteristics.
Material shall be capable of movements
of -25%, -25% (50% total) of nominal material size.
Standard sizes from 1/2" (25mm) to 4" (150mm). Depth of
seal is 4" (100 mm). Silicone coating to be highway-grade,
low-modulus, jet-fuel resistant silicone factory-applied
to the foam while it is partially pre-compressed to a
width greater than maximum joint extension and cured
before final compression. When compressed to final
supplied dimension, a bellow(s) to handle movement must
be created in the silicone coating.
EMSHIELD DFR2 / EMSHIELD DFR3 to be
installed into manufacturer’s standard field-applied
epoxy adhesive. The EMSHIELD DFR2 / EMSHIELD DFR3 is to
be installed slightly recessed from the surface such
that when the field-applied injection band of silicone
is installed between the substrates and the
foam-and-silicone-bellow(s), the system will be
essentially flush with the substrate surface.
Select the sealant system model
appropriate to the movement and design requirements at
each joint location that meet the project specification
or as defined by the structural engineer of record.
Manufacturer’s Checklist must be
completed by expansion joint subcontractor and returned
to manufacturer at time of ordering material. Fabrication EMSHIELD DFR2 / EMSHIELD DFR3 by EMSEAL
must be supplied precompressed to less than the joint
size, packaged in shrink-wrapped lengths (sticks).
Directional changes and terminations
into horizontal plane surfaces to be provided by
factory-manufactured universal-90-degree single units
containing minimum 12-inch long leg and 6-inch long leg
or custom leg on each side of the direction change or
through field fabrication in strict accordance with
published installation instructions. PART 3 – EXECUTION Installation Preparation of the Work Area The contractor shall provide
properly formed and prepared expansion joint
openings constructed to the exact dimensions and
elevations shown on manufacturer’s standard system
drawings or as shown on the contract drawings.
Deviations from these dimensions will not be allowed
without the written consent of the engineer of
record.
The contractor shall clean the joint
opening of all contaminants immediately prior to
installation of expansion joint system. Repair
spalled, irregular or unsound joint surfaces using
accepted industry practices for repair of the
substrates in question. Remove protruding roughness
to ensure joint sides are smooth. Ensure that there
is sufficient depth to receive the full depth of the
size of the EMSHIELD DFR2 / EMSHIELD DFR3 being
installed. Refer to Manufacturers Installation Guide
for detailed step-by-step instructions.
No drilling, or screwing, or
fasteners of any type are permitted to anchor the
sealant system into the substrate.
System to be installed by qualified
sub-contractors only according to detailed published
installation procedures and/or in accordance with
job-specific installation instructions of
manufacturer’s field technician. Clean and Protect Protect the system and its components
during construction. Subsequent damage to the expansion
joint system will be repaired at the general
contractor’s expense. After work is complete, clean
exposed surfaces with a suitable cleaner that will not
harm or attack the finish. END OF SECTION END OF SECTION |
|||||||||||||||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||||||||||||||
|
|
|